| CFM | 6" round | 8" round | 10" round | 12" round | |------|---------|---------|----------|----------| | 100 | 0.18 | 0.06 | 0.02 | 0.01 | | 200 | 0.58 | 0.18 | 0.06 | 0.02 | | 400 | - | 0.58 | 0.22 | 0.08 |
| A | B | C | D | E | F | G | |---|---|---|---|---|---|---| | Section | Q (CFM) | Duct Size (in) | Length (ft) | Fitting Type | Fitting Qty | Pressure Drop (in w.g.) | duct esp calculation excel
If an elbow has EqL = 25 ft and friction rate = 0.08 in/100ft, then dynamic loss = 25/100 * 0.08 = 0.02 in w.g. | CFM | 6" round | 8" round
To calculate External Static Pressure (ESP) in Excel, you must sum the friction losses from straight ductwork, the dynamic losses from fittings, and the pressure drops from accessories along the system's "critical path". the dynamic losses from fittings
| CFM | 6" round | 8" round | 10" round | 12" round | |------|---------|---------|----------|----------| | 100 | 0.18 | 0.06 | 0.02 | 0.01 | | 200 | 0.58 | 0.18 | 0.06 | 0.02 | | 400 | - | 0.58 | 0.22 | 0.08 |
| A | B | C | D | E | F | G | |---|---|---|---|---|---|---| | Section | Q (CFM) | Duct Size (in) | Length (ft) | Fitting Type | Fitting Qty | Pressure Drop (in w.g.) |
If an elbow has EqL = 25 ft and friction rate = 0.08 in/100ft, then dynamic loss = 25/100 * 0.08 = 0.02 in w.g.
To calculate External Static Pressure (ESP) in Excel, you must sum the friction losses from straight ductwork, the dynamic losses from fittings, and the pressure drops from accessories along the system's "critical path".