Under-Frequency Roll-Off slope set to 17% down to 30Hz to prevent engine damage during low-speed operation. 2. Common Adjustments
If the engine sounds like it is "hunting" (revving up and down rhythmically) or if the voltage needle is fluctuating, the STAB control may be set too high
Use the potentiometers on the AVR unit. Turning the P1 potentiometer counterclockwise with a flathead screwdriver will typically lower the voltage. denyo avr nta-5a-2db manual
When a welder or generator powers up heavy machinery, the engine speed (RPM) might dip, or the electrical load might spike. Without an AVR, this would result in voltage drops or surges that could damage sensitive electronics or result in poor welding performance. The senses the output voltage, compares it to a stable reference, and adjusts the excitation current to the alternator's field windings to correct any deviations.
The NTA-5A-2DB usually features a terminal strip where wires connect. While exact terminal numbers vary by revision, they generally follow this logic: Under-Frequency Roll-Off slope set to 17% down to
| Terminal | Function | Connected to | |----------|----------|----------------| | | AC Input (Sensing) | Generator main stator output (L1, L2) | | S, T | Auxiliary Winding Input | Excitation stator winding (sometimes labeled X, Y) | | E, F | Field Output (DC) | Rotor exciter field (brushless exciter stator) | | K, L | Frequency adjustment / Remote voltage trim (optional) | External potentiometer (if used) | | U, V, W | Not used in most single-phase applications | (3-phase sensing backup) |
If the generator isn't putting out steady power, you can test the AVR by checking for fluctuating DC voltage (typically up to 20-30V DC) at the terminals using a multimeter. Common Applications NTA-5A-2DB Go to product viewer dialog for this item. is often found in these specific Denyo generator models: manual - denyo.info The senses the output voltage, compares it to
The official manual emphasizes these life-saving rules:
| Function | How to Use | What to Watch For | |----------|------------|-------------------| | | Use the front‑panel knob (or remote command) to set the desired output voltage within the 220 V ± 5 % range. | The AVR will automatically correct dips/spikes; no manual tweaking needed under normal load. | | Frequency Control | The AVR maintains 50 Hz automatically. Some models allow a ±1 Hz set‑point via dip‑switches. | If frequency deviates, check generator speed sensor and fuel system. | | Load Sharing (Parallel Operation) | When running two generators in parallel, set the “load‑share” dip‑switches to “parallel” mode and ensure identical voltage/frequency settings. | Verify that both AVRs report the same voltage; mismatched settings can cause circulating currents. | | Self‑Diagnostic | The unit runs a self‑test each minute and flashes a fault code on the LED if a problem is detected. | Note the fault code (e.g., “E1 – Over‑voltage”) and act according to the troubleshooting table. | | Remote Monitoring | Connect an RS‑485 master (PLC, SCADA, or laptop) and query the Modbus registers: ‑ 0x0000 – Input Voltage ‑ 0x0001 – Output Voltage ‑ 0x0002 – Frequency ‑ 0x0010 – Fault Code | Use a simple Modbus client to log data or set alarm thresholds. |
| Connection | Color (typical) | Notes | |------------|----------------|-------| | | Red, Yellow, Blue | Connect to generator output terminals. | | N (Neutral) | Black | Connect to generator neutral (if applicable). | | U, V, W (Output) | Brown, Orange, Grey | Connect to load side distribution board. | | Earth/Ground | Green‑Yellow | Bond to chassis ground. | | Control Power (24 VDC) | Usually orange/white pair | Supplies the AVR’s internal electronics; often taken from the generator control panel. | | Communication (RS‑485) | A/B (or +/–) | For optional remote monitoring; terminate with 120 Ω if the line length > 30 m. |